Range | Compact |
Product name | Compact NSX |
Product or component type | Circuit breaker |
Device short name | Compact NSX100M |
Device application | Distribution |
Poles description | 1P |
Protected poles description | 1t |
Network type | AC DC |
Network frequency | 50/60 Hz |
[In] rated current | 100 A ( 40 °C ) 100 A ( 65 °C ) |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 250 V DC conforming to IEC 60947-2 277 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code | M |
Breaking capacity | 40 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 40 kA at 277 V AC 50/60 Hz conforming to NEMA AB1 HIC 40 kA Icu at 220 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 277 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 250 V DC 1P conforming to IEC 60947-2 85 kA Icu at 48/125 V DC 1P conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | Ics 40 kA 220 V AC 50/60 Hz conforming to IEC 60947-2 Ics 40 kA 277 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 250 V DC conforming to IEC 60947-2 Ics 85 kA 48/125 V DC conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit protection functions | LI |
Trip unit rating | 16 A ( 40 °C ) |
Protection type | Overload protection (thermal) Short-circuit protection (magnetic) |
Pollution degree | 3 conforming to IEC 60947 |