Marking | 0 - 1 |
[Ue] rated operational voltage | 690 V AC |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ithe] conventional enclosed thermal current | 100 A |
[Ie] rated operational current | 68.5 A AC-23A 400 V |
Rated operational power in W | 37 kW at 400 V AC-23 30 kW at 400 V AC-3 |
Intermittent duty class | 30 |
Making capacity ( I rms) | 1250 A at 400 V AC-21A 1250 A at 400 V AC-22A 1250 A at 400 V AC-23A |
[Icm] rated short-circuit making capacity | 2.8 kA at 400 V at Ipeak |
[Icw] rated short-time withstand Rms current | 1500 A at 400 V during 1 s |
Rated conditional short-circuit current | 10 kA at 400 V - associated fuse 125 A aM 10 kA at 400 V - associated fuse 125 A gG |
Breaking capacity | 1000 A at 400 V (AC-21A) 1000 A at 400 V (AC-22A) 1000 A at 400 V (AC-23A) |
Mechanical durability | 30000 cycles |
Electrical durability | 30000 cycles AC-21 30000 cycles DC-1...5 |
Environmental characteristic | Standard environment |
Suitability for isolation | Yes |
Connections - terminals | Control circuit : connector cable 70 mm² - cable stiffness: flexible - with cable end cable end Control circuit : connector cable 95 mm² - cable stiffness: solid - |
Tightening torque | Control circuit : 22.6 N.m - on connector |
Fire resistance | 960 °C conforming to IEC 60595-2-1 |
Handle front plate dimension | 90 x 90 mm |
Height | 291 mm |
Width | 241 mm |
Depth | 191 mm |
Product weight | 2.19 kg |