Range | Compact |
Range of product | NSX100...250 NSX100...250 DC |
Product name | Compact NSX |
Product or component type | Circuit breaker |
Device short name | Compact NSX100M |
Device application | Distribution |
Poles description | 2P |
Protected poles description | 2t |
Network type | AC DC |
Network frequency | 50/60 Hz |
[In] rated current | 100 A ( 65 °C ) 100 A ( 40 °C ) |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
[Ue] rated operational voltage | 500 V DC conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity code | M |
Breaking capacity | 85 kA Icu at 500 V DC 2P conforming to IEC 60947-2 85 kA Icu at 220 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 25 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC 85 kA Icu at 48/125 V DC 1P conforming to IEC 60947-2 85 kA Icu at 250 V DC 1P conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service breaking capacity | Ics 85 kA 220 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 85 kA 240 V AC 50/60 Hz conforming to NEMA AB1 HIC Ics 25 kA 480 V AC 50/60 Hz conforming to NEMA AB1 HIC Ics 18 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 Ics 18 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 Ics 10 kA 600 V AC 50/60 Hz conforming to NEMA AB1 HIC Ics 8 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-2 |
Utilisation category | Category A |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit protection functions | LI |
Trip unit rating | 16 A ( 40 °C ) |
Protection type | Overload protection (thermal) Short-circuit protection (magnetic) |
Pollution degree | 3 conforming to IEC 60947 |